Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
DPD-2 reagent expired. Replace reagent. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level high. Maintain water level so that skimmers operate correctly. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Flow meter leaking for chlorinator. Replace/repair. Intent to Suspend issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Pump not meeting turnover. Permit restriction - flow meter must remain operable. Flow required at 128 gpm to 200 gpm to meet turnover and flow restriction of the number of returns. Intent to suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Floor drain in pump room not draining. Holding water. Floor shall drain properly. Intent to Suspend issued.
.2533(d) Pump room floor shall be kept dry and free of standing water. |