Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameWESTMORELAND
Address9500 ROSALYN GLEN DR
 
City/State/ZIP
CORNELIUS NC 28031
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 5/29/2026
Final Score @ Grade
4
General CommentsOSV to pool for return construction with Alex Novotny, Connor Construction for return construction. Scope of Work - Pool renovated with profile changed. No renovation to pump room, chemical storage room, and restrooms. New equipment in pump room. Permit issued for no night swimming. Holds released on project. Permit Restrictions: 1) Filtration Pump VFD installed. Flow meter must remain operable. Flow required at 234 gpm to 282 gpm to meet turnover and flow restriction of the filters. 2) No seating behind umbrella so that pole blocks any part of the pool interior. 3) Portable vacuum required. No vacuum line plumbed. 4) Backwash valve required to be limited with screw to ensure pit can maintain flow from backwash. Notes: 1) Two sets of safety equipment required. 2) Bather load limited to 200 due to existing fixture count in the restrooms. Back side of backwash pit with concrete still setting. Still appears wet. No leaks with backwash. Slab repaired. No water coming through floor during backwash. Leak from day prior indicates that there may be a break in the line. Permanent repair may be required if backwash pit does not drain adequately or if leak through pump room floor persists. Max Depth 5 ft.; Pool Width 82 ft.; Rope Length 50 ft. Filtration Pentair EQK 500, 5 hp pump. Feature Hayward HCP 3000 Series HCP3020 VSP, 2.7 THP pump Both pumps are tied into the same set of main drains Daldorado Dalmax SG-183625 2017 drain covers. EQ lines plugged in skimmers.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Light burnt out in chemical storage room. Repair light. Chemical storage room not accessible. Chemical tanks block back shelving where bicarb is stored. Keep clearance in chemical storage room so chemicals are accessible.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Umbrellas stored in shower in women's restroom. Shower shall remain accessible. No toilet paper in one stall in women's restroom. Corrected during the inspection.