6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
One screw missing from left Aegis drain cover. Drain cover is secure. Given one week to correct. Picture documentation ok. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
(4) skimmer baskets stuck. Aquatech able to get one removed. (2) skimmer baskets after bball hoop near steps and (1) on the right side of the pool. Skimmer baskets shall be easily removed to ensure baskets are emptied. Could not verify plug in equalizer line.
Intent to Suspend issued. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Right handrail at step entry loose. Tighten. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy at zero entry with rope tangled. Corrected during the inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate on exterior barrier near lazy river pump room not self-closing, self-latching. Repair to self-close, self-latch. Intent to Suspend issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable. Flow meter shall remain operable. Flow required at min of 391 gpm. Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemical storage for new pump room area located outside. Area is not inaccessible to the public. Gate installed but not kept locked. Chemical storage shall be inside and storage area shall meet storage requirements of chemical storage room.
.2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft. Intent to Suspend issued. |