Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Pool has permit restriction for the circulation system where vacuum gauge and pressure gauge must be properly installed so that TDH can be measured. Also, valve handle was found in a new position relative to the previous position it should be in. This new position appears to open up the valve more. Return the valve to the previous position. The vacuum gauge must be replaced and the valve handle returned to the previous position and secured there with the padlock. Immediate Suspension issued. Contact C. Elmore (704-507-6814) when the correction is made. Pool is closed to swimming by order of the Health Department until the correction is verified. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed typographical error in the phone number. Corrected to 205-983-3411. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms > 110 F. .2526(i) Water in restrooms shall not exceed 110 F. |