| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
A10RCFRxxx drain covers rated at 119 GPM. TDH calculation after a backwash is 130 GPM. Will need to change covers and submit updated PDSC form. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir missing styrofoam insert, not functioning. .2518(k) Provide functional weirs. - Immediate suspension item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Second step missing non-slip tread. .2521 Install ladders per manufacturer instructions.
Ladder > 6” from pool wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Eyeball fitting assembly missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Immediate suspension item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Throw rope 39 feet long. .2530(a) Provide US Coast Guard approved ring buoy with 33 foot throw rope. - Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door from office not self-closing and self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Vacuum cap damaged, can be opened without a tool. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Immediate suspension item. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Restrooms only accessible when the office is open. .2526(a) Provide at least one sink and toilet for residents and guests if furthest unit is more than 300 feet from the pool at hotels, motels, condominiums and apartments. - Facility working to install keyfob entry for door that opens on to pool deck from restroom hallway. Will need to be completed prior to permit being issued. - Immediate suspension item. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms > 110 F. .2526(i) Water in restrooms shall not exceed 110 F. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib on pool deck missing a backflow preventer. .2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. |