Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
Observed both equalizers in skimmer baskets without plugs. According to PDSC form, establishment should have both equalizers lines disabled. CPO should ensure properly fitted plugs on both lines. |
|
14
|
4
|
Pool maintenance: spa timer working properly |
No |
No
|
No |
.2537(b) Spa times shall not exceed 15 minutes without manual resetting.
Observed timer not shutting off jets after 15 minutes. Repair so that jets do not run for longer than 15 minutes with each cycle. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water.
Observed leak at water heater for spa causing standing water about 1/2 inch in back of pump room. Remove water and repair leak. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
.2518(d) Piping and valves shall be labeled with color codes or labels.
Observed pipes to spa not directionally labeled. EHS advises PIC to correct ahead of re-inspection. |