Inspection Date 3/31/2026
Final Score @ Grade
20
General CommentsInspection conducted with CPO Daniel Ubiles. Pool recently had new coping and wall tiles installed. Polymetric sand not yet added. Ensure that deck is structurally sound with no gaps or offsets > 1/2 inch. Area above one of the skimmers missing underlayment to keep Polymetric sand from falling into the skimmers. Ensure that this is permanently addressed with a product designed for this purpose. Must be corrected within 30 days or permit will be suspended. Immediate suspension still in place. 3) Contact Will Harrison (704) 507-6824 for re-inspection once issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No PH < 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One weir missing, the rest of the weirs stuck, do not move freely. .2518(k) Provide functioning weirs. - Intent to suspend item.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Polymetric sand missing between coping and deck. Some deck pavers loose or missing. .2537(2) Decks shall be structurally sound and kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. - Intent to suspend item.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Chemical controller reading 7.4. Got < 6.8 on my test kit. Ensure chemical controller is properly calibrated. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Some items stored by pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.