24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate.
Observed flow meter maximum reading 240gpm with max flow for pump as 225gpm. Replace with flow meter capable of measuring up to 340gpm.
CPO should replace and verify with EHS within 30 days. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Observed bagged chemicals on floor in chemical storage room. Provide crates, risers, or other means of bringing chemicals off the floor. |