General CommentsConducted inspection with CPO Manuel. Intent to suspend issued. Intent to suspend items must be fixed prior to June 1st or pool will have to close. Call EHS Devon when ready 7049981122 Note: 3 side gates permanently closed. Operable gates include two entrance gates on either side of clubhouse and back gate leading to pickleball court. Upper structures are fountains. Construction Date 1/1/1985 Rope Length 27ft Permit Restrictions: 1) Both systems required to have operable flow meters. 2) Pump 1 - Fountain and Lower Pool - Pump shall be kept at 54 gpm to 98 gpm to meet turnover and flow restriction of the filter. 3) Pump 2 - Upper Pools - Pump does not meet turnover at 83 gpm due to flow restriction of the number of returns. Pump required at 80 gpm. (2) stepping stone SDX2 drain covers not operable per Caribbean - no suction. 2 drains in lower pool - 4 drains in upper pools - 2 drains in small fountain feature are. 10 drains total with 2 not operable. SDX2 drain covers in the stepping stones - installed 6/1/2024.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2528(a) Provide no openings in fence and/or gate greater than 4"x4" and shall provide no external handholds or footholds. Two openings greater than 4” at gates on either side of the clubhouse. Old handles on gates (not in use anymore) protrude more than two inches and are below 40” creating footholds. Intent to suspend items.
22 6 Premises: emergency telephone provided No No No .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Posted callback number incorrect. Verified correct number with emergency department. Operator posted correct number. No permit action.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No .2518(g) Keep flow meter operational. Flow meter on Pump 1 exceeds allowable range. Must be between 54gpm and 98gpm. Flow meter not working on Pump 2 upper pools. Flow meter must remain operational and read at 80gpm. Intent to suspend items.