| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records, missing man drain checks.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. operator added Main, drain checks, and corrected. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir stuck at time of inspection. Some skimmer baskets observed with debris.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
.2518(k) Keep weirs in good repair. Operator cleaned baskets and adjusted weir. Corrected. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chairs within 6 foot of pool.
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Operator moved in corrected.
General comment: There is a small area that is starting to crack by ladder. Advised sealing to eliminate offset greater than half inch before next inspection. Currently in compliance. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Signage missing the word ”the”. .2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. operator had old signage in pump room, and posted. Note: If signage is replaced ensure Code is met and posted in area where it is clearly visible from all areas of pool. Old signage is covered by bush. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No 3’ clearance in pump room. Chemicals stored and in use in pump room. Ventilation not continuos in pump room.Pool built 1996. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Labeling has faded off, piping in pump room.
.2518(d) Piping and valves shall be labeled with color codes or labels. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Showers off at time of inspection. .2526(h) Shower(s) shall be provided. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No toilet paper in women’s restroom. .2526(l) Provide toilet paper and dispensers in restrooms. Operator added in stalls and corrected. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in pump room observed without anti-siphon device. .2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. |