6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. Drain covers are only approved if filter pump flow is below 138 gpm. Flow observed on flow meter during inspection was above 180 gpm. CDI - Operator adjusted variable speed pump and reduced the flow on flow meter to 120 gpm during inspection. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Debris present on bottom of pool |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Clean debris out of skimmer baskets. |