| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool wall tiling missing, damaged in multiple places. .2537b(8) Damaged face plates or fittings shall be repaired or replaced.
*Permit item |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
2 of 4 weirs missing.
.2518(k) Replace missing weirs.
*permit item |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Rope to buoy tangled and inaccessible for emergency. Operator untangled and corrected.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
.2530(a) Lifesaving equipment should be conspicuously and conveniently located. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate at front and side not latching at time of inspection.
.2537(b) All gates and doors shall be self-closing, self-latching.
*Permit item
Fencing by back side gate has original construction, horizontals less than 45” in height. Pool built 1999.
.2528(a) Horizontals shall not be located less than 45" in height. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Coping cracked greater than 1/2”, not secured and loose.
.2537(2) Decks shall be kept in good repair.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
.2537(3) There shall be no loose coping.
*permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
No spare pump baskets for either pump. Pumps: Sta Rite P6RA6G-207L and Pentair CHII-NI-2FE
.2518(e) Provide a spare basket for pump.
*permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals in pump room. No 3’ clearance. Original construction.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Labeling on piping faded, not identified. .2518(d) Piping and valves shall be labeled with color codes with a legend or labels. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Observed shower non operational. 2526(h) Shower(s) shall be provided. |