13
|
4
|
Water availability, pressure, at required ranges |
No |
No
|
No |
Observed hot water reach 129F
**15A NCAC 18A .1611 (d) Residential care facilities shall provide water heating facilities. Hot water shall be provided at temperatures between 105F and 116F at handwashing and bathing facilities. |