2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed 0.1ppm free chlorine. .2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator. - Immediate suspension item. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
PH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form on file does not match the currently installed filtration drain covers. .2539(d) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Documentation shall include an accurate Pool Drain Suction Compliance Form. - Immediate suspension item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate to restrooms propped open. .2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some chairs and furniture within 6’ of pool. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Intent to suspend item.
Pedestal pool, many of the tiles loose. .2537(2) Decks shall be structurally sound and kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some of the labeling has worn off. .2518(d) Piping and valves shall be labeled with color codes with a legend or labels. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Light out in one of the restrooms. .2526(m) Keep restrooms and fixtures clean and in good repair. |