Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameWAYFORD AT INNOVATION PARK
Address1018 CATALYST BLVD
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 7/1/2024
Final Score @ Grade
28
General CommentsInspection conducted with CPO Teron Watkins. Chemical hazard signage does not note the type of chemical hazard in chemical storage room. Recommend installing Chemical Safety Placard on pump room and chemical storage room doors. Can check with Fire Marshall to ensure correct type is installed. Permit condition - Pool bowl shaped. 4 foot along pool wall, but 4 foot 6 inches deep in the middle. Permit condition that signage must remain in place in the pool area letting bathers know. Pemit condition - Pump required to be at max speed. Pump does not meet turnover by 4 GPM (119 GPM). If clarity or chemistry issues occur due to lack of turnover a properly sized pump will be required to be installed. - Verified PUMP at max speed today, but only at 85 GPM. - Will follow up on next visit. Intent to suspend issued 5) 8) 16)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No 0.4ppm free chlorine. .2535(4) Maintain chlorine at least 1.0 ppm. - Corrected to 1ppm.
3 6 Water quality: pool water pH No No No PH > 8.4. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.5.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No recent main drain, total alkalinity or cyanuric acid checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Water level below the skimmers. Skimmers turned off in the pump room. .2518(k) Water level shall be maintained to assure skimmers are operable. - Intent to suspend item.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Doors to restrooms not self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No All chemicals currently stored in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Bag of chemicals stored on pump room floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Out of toilet paper in one of the women’s stalls. .2526(l) Provide toilet paper and dispensers in restrooms.