| Name | SYMPHONY PARK | | Address | 12227 SAM FURR RD
| | | | City/State/ZIP | | | Premise Type | 53 - Year-Round Swimming Pool | | County | Mecklenburg | | Inspection Date
| 6/10/2024 | | Final Score @ Grade | | | Onsite visit to pool with Mason Garrett, Hot Springs Pools, and Tim Boatwright, Carolina Commercial Contractors, for construction final. Deck damage at far corner tie into coping on step entry side of pool closest to courtyard. Contractor used extra decking to repair the damaged area. Ensure repair is set. EHS will verify during follow-up inspection.
Construction final passed. Holds released in system. Permit has been issued for night swimming. A follow-up inspection will be completed by assigned EHS within 30 days, after July 1.
Note:
1) Floor in pump room beginning to crack again. Monitor. May require repair in future if worsens.
2) Check valve not installed with catch drain per plumbing code. Floor in pump room required to be kept dry and sloped to drain. Previous site visit - Move check valve to ensure a catch drain can be located under the check valve and plumbed to the backwash pit for drainage. No catch drain installed. Recommendation to install catch drain to eliminate water on the pump room floor.
3) Heater not on at time of inspection. Ensure water does not exceed 90 F.
4) Pool operator sick at time of inspection but came by pool to provide CPO card. Pool must remain closed if pool operator is not onsite. Only one CPO certified operator for the facility.
Max Depth 4 ft.; Pool Width 25 ft.; Rope Length 37.5 ft.
Permit Restrictions: 1) Pump shall be set at 3450 RPM or flow meter must remain operable with flow at 102 gpm to 138 gpm to meet turnover and flow restriction of suction pipe sizing. 2) Pool approved with logo.
Pentair Intelliflo3 VSF 011075, 3 hp pump with (2) Hayward WG1031BHF2 VGBA-2017 drain covers. EQ lines capped on underside plugged in skimmer. |
|