Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 8.2 in pool at beginning of inspection. Water pH was corrected and measured at 7.7 after an hour. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed pool records without recording of weekly cyanuric acid. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed one missing weir on skimmer at 3 1/2ft depth near pool steps. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed pool with two buoys and buoy ropes. Pool is 2800 sqft and is only required one set of life saving equipment. Buoy ropes were in disrepair, one rope around buoy was broken and second buoy rope was brittle and crumbled upon handling. CDI - Buoy rope was replaced for buoy that had broken rope and one fully compliant buoy was created during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching. Observed entrance gate unable to self latch and self-close |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(b) Provide sufficient lighting in pump room. Observed no working lighting in pump room
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed standing water in pump room floor. |