2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine at 0.6 ppm. Operator turned up feeder while onsite but chlorine did not correct. Maintain chlorine at least 1.0 ppm through approved NSF chlorinator. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Some months with CYA and Total alkalinity readings not weekly. Ensure weekly record keeping.
Total alkalinity reagent expired. Replace reagent. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Algae build-up on plaster on walls, between contrasting color band grout, and around main drains. Continue to monitor and treat as needed. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level low, just at skimmer line. Ensure water level is high enough to ensure skimmers are operating per NSF requirement. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Body hook not secured to pole. Corrected during the inspection.
Grab rope on ring buoy starting to deteriorate due to weathering. Replace ring buoy with USCG approved buoy. Immediate Suspension issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet. Operator bled filter after backwash. Ensure floor kept dry. Could not identify any leaks.
Some chemicals stored in pump room. Ensure all chemicals stored in chemical storage room.
Fan turned off in pump room/chemical storage room. Turned on during the inspection. Ensure forced draw ventilation is operable at all times. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No soap in men's restroom. Provide soap. |