11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder missing rubber cap at deep end.
.2521 Install ladders per manufacturer instructions. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Two ring buoys and ropes present on pool deck. One ring buoy rope length is out of compliance. Operator removed incorrect ring buoy and rope from pool deck. One compliant ring buoy and rope remains on pool deck. No permit action. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pool built in 1975. Door to pump room not locked at time of inspection. No clear walking space around equipment. Chemical stored in pump room. Some water on floor around filter. Piping goes outside of equipment room. No drain observed in pump room. No backflow prevention on hose bib.
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(d) Provide drain in pump room floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Pool built in 1975. No air gap observed at backwash. .2513(b) Filter backwash shall be discharged through an air gap. |