3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. EHS observed pH at 8.4. Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(h) Provide approved pump in good repair. Pump not meeting requirements of flow restriction. EHS observed flow at 95gpm. Operator unable to correct in field. Flow shall be maintained at 68gpm to 80gpm to meet turnover and flow restriction with number of returns. Immediate suspension item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Chemicals stored in pump room. Move to designated chemical storage room.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Bag of chemicals on ground in chemical storage room. Raise off floor. |