1
|
1
|
Floors and carpets cleanable, clean, good repair; carpet odor free |
No |
No
|
No |
REPEAT
1309 (a) and (b) The floors in an institution shall be made of smooth, non-absorbent materials and shall be kept clean and in good repair. When carpet is present, it must be kept clean, odor free, and in good repair.- Observed dust/debris on flooring and underneath the beds, behind furniture throughout the facility. Keep all floors clean and keep clean. Half point deducted due to improvement. |
|
10
|
0
|
Handwashing facilities properly located and equipped |
No |
No
|
No |
General Comment:
.1312 (d) Handwashing facilities shall be supplied with soap and disposable towels or hand-drying devices.- Observed no paper towels available at general hand sink in A 211, restroom E 208 and D 209. No soap available in a dispenser at general hand sink in E 208. Ensure to provide all hand washing supplies at all hand sinks at all time. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
REPEAT
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities.- Observed hot water temperature throughout the facility measured out of required range either too low or too high. Some start off right at 115F and going down to 88F D hall 209. Some start low temperature at 88F and going up to 121F C hall 203. In restroom C 203 is 90F. E 208 at 141F. Restroom B hall at 84F. Med tech room at 57F. A 113 measured at 125F, A 105 measured at 140F. Salon room: 144F. Activity room 118F in one sink and the other is 142F. A 211 at 119F. B Hall 202 at 98F. C 103 at 91F, D 105 at 88F, and D 106 at 90F. The facility shall provide water temperature between the range of 105F - 116F. Points remain the same at this time. |
|
18
|
0.50
|
Drinking fountains clean, good repair |
No |
No
|
No |
.1314 (a) Drinking fountains shall be kept clean and in good repair.- Observed soiled water fountain in therapy room need better cleaning all around surfaces, spouts and crevices. Cleaning needed and Keep clean. |