Premises Information

Return to Inspections
NameAXIS AT THE PARK
Address5200 OXFORD POND DR
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 10/20/2026
Final Score @ Grade
44
General Comments6 - Drain covers replaced. Viewed old drain covers in the pump room. New covers 2017. PDSC form does not reflect new covers and installation dates. Require new PDSC form within 1 week or permit will be suspended. Original construction/plumbing inspection shows 8" pipe to T then reduces to 6" pipe back to the pump room. New 2017 Lawson 18x18 drain covers require 8" pipe for at least 40" before reduction. Measured 10 ft. between drains prior to reduction to 6" pipe. Meets mfg. requirements. Intent to Suspend issued for: .2535 - Cyanuric acid reagent expired. No main drain checks. CYA approx. 110 ppm. Replace reagent, ensure daily record keeping for main drain checks and lower CYA to 100 ppm or less. .2538 - repair front gate to self-close, self-latch. .2533/.2537 - repair damaged piece of coping. .2530 - Move Warning No Lifeguard on Duty inside of barrier so visible from all entries into the pool. .2518 - install flow meter per mfg. instructions with correct inlet/outlet lengths of straight run pipe. Move ring buoy/rope and body hook that is blocked by landscaping so accessible within 30 days. Michael St. John new CPO. Viewed CPO certification while onsite. NOTES: 1 Pumps remain set at 3450 RPM or flow shall remain at 242 gpm to 396 gpm to meet turnover and flow restriction of return pipe size. 2)Fence along back of retaining wall ok at >2” due to height of retaining wall. 3) Hose bib for restrooms is located on outside wall.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Cyanuric acid reagent expired. No main drain checks. CYA approx. 110 ppm. Replace reagent, ensure daily record keeping for main drain checks and lower CYA to 100 ppm or less. Intent to Suspend issued.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Some algae build-up on pool walls and around ladders. Keep pool clean. Monitor and treat as needed.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No All skimmer baskets full of debris. Emptied during the inspection.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Body hook/ring buoy with 50 ft rope on back side of pool not accessible due to landscaping. Move body hook/ring buoy within 30 days. One ring buoy rope tangled. Keep accessible in case of emergencies. Corrected during inspection.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Main gate into pool at parking area not latching. Repair gate to self-close, self-latch. Intent to Suspend issued.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Coping cracked and broken off at left side of pool near ladder. Repair coping. Intent to Suspend issued. Multiple areas where deck is cracking, coping caulking is damaged or separating. Deck appears to be moving. Skimmer closest to clubhouse near ladder with slight offset around skimmer. Monitor. If offsets or damage are >1/2", repair will be required.
18 4 Premises: lifeguards present or warning signs posted No No No Warning signage located outside of the main pool gate. Re-locate signage so visible upon entry to pool from all entrances. Intent to Suspend issued.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Chlorine/acid line into return line leaking. Leak did not warrant repair at time of inspection. Repair leak to ensure pump room floor remains dry.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter installed does not meet 10% accuracy requirement. Not installed per mfg. instructions. Flow meter on 4" line and requires 20" of straight run pipe before the flow meter and 8" after. Digital flow meter is located within required straight run pipe. Intent to Suspend issued. Install flow meter per mfg. instructions.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Pump room floor wet due to leak at feeder lines into the return line. Keep pump room floor dry.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Men's restroom door locked from inside. Keep accessible. Men's restroom with no soap. Provide soap for handwashing.
30 2 Dressing and sanitary facilities: approved water source, no cross connections No No No Aufofill float has been removed from inside of the autofill and not working. Repair autofill so functional.