Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records missing weekly cyanuric acid. Pool has been closed since 2023.
.2535(11) Provide weekly recordings for cyanuric acid and total alkalinity. Operator added to records and verified records have all required field. Corrected. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
New buoys with ropes not cut, too long at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator corrected both to 36’ rope and removed old buoy. Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Grill area outside of pool barrier provide footholds. Eliminate footholds. Pool built pre-2010.
.2528(a) Horizontals shall not be located less than 45" in height.
Gap in fencing by emergency phone greater than 4”.
.2528(a) Provide no openings in fence and/or gate that allows passage of a four inch diameter sphere.
Operator closed gap and corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Limited space for walking around equipment due to storage of chemicals in pump room. No clear walking space around equipment. Ventilation not working in pump room. No light in chemical storage room.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(6) Provide sufficient lighting in chemical storage room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in restrooms. Provide within 50 ft. of restrooms. Original construction. |