Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed water to be at 8.1 pH upon arrival. pH was corrected to 7.8. CDI |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed 2 weirs missing out of 4 total. No Permit Action as 50% of weirs are still in place. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide at least 12 ft. long pole with body hook securely attached.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed 38 ft. Throw rope when 45 ft. Is required for this pool. -CDI corrected to proper length.
Observed no bolts in body hook to secure it. CDI Bolt with nut was added. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed sections of fencing at the units with patios that are next to the pool deck to have barriers that are not to current specifications. The barrier is pre 2010. 100 ft. Out of 312 ft. Was recently replaced with new fence. No Permit Action taken. |