8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
No flow through some of the far skimmers. Recommend cleaning out the line. .2518(k) The flow-through rate through any one skimmer shall be between 20 GPM and the maximum flow rated under NSF 50.
Some skimmer baskets full of leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladders extend > 6” into the pool. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Missing one eyeball fitting. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Pre-2010 fence < 48” high in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some labeling worn off or missing. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |