Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAVANT AT STEELE CREEK II
Address12918 WINTER HAZEL RD
 
City/State/ZIP
CHARLOTTE NC 28278
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/7/2023
Final Score @ Grade
40
General CommentsInspection conducted with operator Randy. Immediate suspension of permit issued due to pool Ph and removal of equalizers and change of drain covers without re-submittal of required PDSC. Submit PDSC with current information on equalizer removal and drain cover information to pdsc@mecknc.gov. Once PDSC is approved and pool chemistry is in compliance, call Hope McIntosh at 980-229-7549 to schedule a return visit. At that time other permit items noted in the inspection will be re-evaluated and if not in compliance a 30 day intent to suspend may be issued. Pool must remain closed with signs posted for no swimming until permit is re-instated.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No .2535(1) Maintain pH at 7.2 to 7.8. Pool water pH at 8.0. *immediate suspension item
6 6 Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ No No No .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. During re-plaster equalizer lines have been disabled and covers removed and main drain covers have been replaced. A new PDSC form must be submitted to the department for approval. *immediate suspension item
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No .2537(14) Keep pool surface and pool floor free of debris. Leaf litter and debris in pool bottom
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Leaf litter and debris in skimmers
9 4 Pool maintenance: depth markings and no diving markers or signs visible and properly located No No No .2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Pool has been re-surfaced. During this process some depth markers and no diving tiles have been moved. Distance between 4 1/2 ft depth markers t26’6”. distance between each of the 3 1/2 ft depth markers on far end of pool 26’4” and 27’. Maximum distance allowed between depth should be no more than 25’. Correct. *permit item
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No .2521 Install ladders per manufacturer instructions. Missing end caps on ladder on left side of pool.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope at 44’. Operator corrected to 45’.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2537(b) All gates and doors shall be self-closing, self-latching. Gated entrance to left of pool currently pad-locked shut. EHS unable to determine if gate self-closes and latches. Pad lock is not permanently disabling gate. Gate must be accessible for testing to ensure self-closure and self-latching or it must be permanently fixed shut (similar to other gate on right side of pool). EHS recommends ensuring permanently fixing this gate shut does not violate other agency codes (like fire code) prior to permanently modifying the gate. *permit item
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Bags of dry chemicals on floor.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No .2526(j) Provide soap and soap dispenser, no glass, at each sink. .2526(l) Provide toilet paper and dispensers in restrooms. .2526(m) Keep restrooms and fixtures clean and in good repair. Both restrooms in need of cleaning. No soap available in either restroom. No toilet paper available in womens restroom.