9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Overlay depth markers on deck not slip-resistant. Removed during the inspection. All deck depth markers shall be slip-resistant.
Wall depth marker at 2 ft. 6 in. with some lettering worn off. Corrected during the inspection. Filled in with permanent marker. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Double doors into pool deck not latching. Magnet latch. Doors leading into the hall before the restrooms are self-closing, self-latching. Door on right side must remain locked. Given one week to repair the doors directly on to the pool deck. Doors shall self-close, self-latch. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Storage in chemical storage room so chemicals not easily accessible. Maintain chemical storage so that the chemicals can be easily attainable.
Fan in pump room does not appear to be operable. Ventilation shall be provided in pump room and chemical storage room.
Pipe from pump to filter runs across floor. Provide 3 ft. clearance around all equipment so that valves/equipment is accessible without trip hazard. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash plumbed directly into pipe. Provide air gap at backwash line to pit. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >114 F. Maintain at 110 F or below. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in pump room without backflow prevention. Provide backflow prevention device on hose bib. |