Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not easily accessible. No records for main drain checks or cyanuric acid. Maintain daily record keeping for main drain checks and weekly record keeping for cyanuric acid. Intent to Suspend issued. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Vinyl liner beginning to bubble at steps. Continue to monitor. May require repair if worsens. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One of two skimmer baskets with debris. Keep skimmers free of debris. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Depth marker peeling off wall at shallow end and missing on pool deck. Provide 2 1/2 ft. or 2 ft. 6 in. on pool wall and pool deck. Intent to Suspend issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable. Repair flow meter. No flow restrictions on pool.
New filter installed. Filter is SD-80 which is for Residential use and not NSF approved. No air relief valve on filter. Filter shall be NSF approved with air relief valve. Given until 2024 operating permit to replace (April 30, 2024). Prior to installation, get approval from Health Department. Design flow of pump at 65 gpm. Filter shall be commercial grade and rated for at least 65 gpm. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash line to pit. Original construction. Provide air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >115 F. Maintain at 110 F or below. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in pump room without backflow prevention device. Provide backflow prevention device. |