Premises Information

Return to Inspections
NameGATEWAY WEST APARTMENTS
Address902 W 4TH ST
 
City/State/ZIP
CHARLOTTE NC 28202
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 8/4/2023
Final Score @ Grade
34
General Comments6 - PDSC form shows 4 skimmers. 2 skimmers installed. Feature pump with no label. HP on pump shows 2.25 THP. PDSC form indicates feature pump a 3210EE, 1 hp pump. Worst case scenario, pump is a 3220EE, 2 hp pump. Provide updated PDSC form for feature with correct model number. No suction hazard. Provide corrected PDSC form within 1 week or permit will be suspended. Intent to Suspend issued for the following: .2528 - eliminate foothold at gate latching mechanism; kick plate provide horizontal at <45"; plexiglass not secure in some places where horizontals at <45" .2518 - secure skimmer collars A return visit will be made in 30 days to verify completion of ITS items. If not corrected, permit will be suspended.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Some sand on the pool floor. Keep floor clean.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Collars around the top of the skimmers loose. Secure. Intent to Suspend issued.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No One gate missing metal angle on gate latching mechanism. Provide 45 degree angle over latching mechanism to eliminate foothold. Some areas where plexiglass is not secured and less than 45" between horizontals. Re-secure in areas missing metal attachment. <45" between horizontals due to kick plates on two gates. Eliminate kick plate or eliminate horizontal by covering outside of gate. Intent to Suspend issued for above items. One gate not self-closing, self-latching. Corrected during the inspection.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Deck drain popped in one location. Corrected during the inspection. Continue to monitor deck. Some polymeric sand beginning to wash out. Repair as needed. Deck is required to have polymeric sand within 6 ft. of pool. Continue to repair remainder of deck.
22 6 Premises: emergency telephone provided No No No No dialing instructions at pool phone. Corrected during the inspection.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No No flow meter on the chlorinator. Original construction. Provide flow meter.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter not operable. No flow restrictions. Repair flow meter so operable.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Floor wet in pump room. Keep dry. Did not view any leaks. Operator stated from backwash.
30 2 Dressing and sanitary facilities: approved water source, no cross connections No No No No backflow prevention device on hose bib in pump room. Provide backflow prevention device.