| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Greater than 25 ft. between wall and deck depth markers around step entry due to "jut-out" at both step entries. Greater than 25 ft. between no diving marker. Maintain at 25 ft. apart or less around pool perimeter. Intent to Suspend issued. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
>75 ft. between handrails from step entry around bench are to ladder handrails. Original construction. Provide handrails at 75 ft apart around pool perimeter. |
|
13
|
4
|
Pool maintenance: contrasting band on steps and benches |
No |
No
|
No |
>1" from edge of step to contrasting band around handrail mounts on steps. Maintain 1" or less from edge of step to tile or provide 2" contrasting band painted to edge of step. Intent to Suspend issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One gate not self-closing, self-latching. Repaired during the inspection.
3/4" between post and gate on front glass entry. Original construction. Maintain 1/2" or less between post and gate. Pool built pre-2010. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
<6 ft. from ladder handrails to pool furniture. Maintain 6 ft. clearance around the pool in all locations. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Signage missing "swimming pool". Corrected with computer generated lettering to read "Children should not use the swimming pool without adult supervision" in 1" lettering. If a new sign is provided, provide correct wording in 1" lettering.
Warning signage blocked by umbrella upon arrival. Umbrella moved. Signage must be clearly visible. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Pump not running at max speed. Turnover for pool is 189 gpm. Design flow of pump is only 155 gpm. If clarity issues occur, pump may be required to be changed to meet turnover.
Flow meter installed does not meet 1.5xdesign flow of the pump. Previous flow meter installed on a 3" pipe. Install flow meter capable of 1.5 x design flow of the pump. Flow meter shall be capable of reading at least 233 gpm. Intent to Suspend issued. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in pump room without backflow prevention device. Provide backflow prevention device.
Water line to fill line and shower without check valve. Original construction. Water introduced to the pool shall be protected by an approved check valve. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in temporary restroom. |