| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
PH 7.0. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Test kits expired. .2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. - Intent to suspend item.
New CPO. Spotty records. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy damaged. Throw rope heavily knotted. 38 feet long. .2530(a) Provide USCG approved ring buoy with attached 50 foot throw rope at least 1/4” in diameter. - Immediate suspension item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Magnetic paddles < 45” high. .2528(b) Horizontals shall not be located less than 45" in height. - Intent to suspend item.
Pre-2010 fence as short as 43” high in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Fill spout located more than 6 inches from ladder. Hole in the deck where spout used to be. .2512(c) Over the rim fill spouts shall be located under the diving board or within six inches of a ladder or handrail and be at least two pipe diameters above the deck or pool overflow level. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. - Intent to suspend item.
Piece of coping by ladder loose. .2537(3) There shall be no loose coping. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed 2” flow meter installed on 2 1/2” return line. .2518(g) Install flow meter on return line per manufacturer instructions such that flow meter is capable of reading 1.5 times design flow rate and within +/- 10% of true flow. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
.2533(b) Provide sufficient lighting in pump room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap on backwash line. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Toilet paper dispenser missing in men’s restroom. Toilet paper sitting on the floor. .2526(l) Provide toilet paper on a dispenser in restrooms.
Out of toilet paper in one of the women’s stalls. .2526(l) Provide toilet paper and dispensers in restrooms. |