8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Missing 2 of 5 skimmer weirs. Replace. No permit action at this time as more than 50% of weirs in place.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Large rock in skimmer basket blocking significant portion of flow. Operator noted is to keep basket in place. Remove. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible. Body hook on adjustable telescoping pole. Operator moved hook to 12’ long non-adjustable pole.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope at 48’. Corrected to 50’.
.2530(a) Lifesaving equipment should be conveniently located. Ring buoy rope tied together limiting use in the case of emergency. Do not tie rope together. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Pool chairs removed from Sun shelf in pool sitting on edge of pool. Lounge chairs pulled up to within 6’ of pool. Provide 6’ of clear space around pool. Operator corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Flow meter not consistently reading flow. Buildup visible. Operator unable to clean out during inspection. EHS will return to evaluate within 30 days. Pool does not have a variable speed motor. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Ventilation system for both pump room and chemical storage room turned off at switch. Systems operates but is very loud when turned on. Repair to allow continuous ventilation in both rooms. |