Water quality: pool water pH |
No |
No
|
No |
Spa pH >8.4. Chemical feeder reading 7.7. Maintain spa pH at 7.2 to 7.8. Chemical feeder shall be calibrated so maintaining spa chemistry correctly. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Missing logs from January 9th. Ensure daily record keeping for chlorine, pH, main drain checks and temperature logs.
No logs for December visible. Spa was closed to the public. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level low. Multiple previous visits where water level is low. Water level below the skimmer line. Water level shall be kept above the skimmer line so that skimmers are functioning per NSF requirement. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Main door entry into locker room with door not latching. Repair door to self-close, self-latch.
Could not access back emergency door. Operator shall demonstrate door self-closes, self-latches.
Door in between pool and locker rooms propped open. Keep door closed so that door is latched and closed. Corrected during the inspection. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
NSF automated feeder reading 7.7 with spa pH greater than 8.4. Calibrate feeder so pool chemistry is balanced.
Operator not present. Automated feeder could not be verified. Feeder shall detect flow and turn off when no flow detected. Operator shall demonstrate. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some chemicals stored in the pump room (granular, muratic, etc). .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Piping for automated feeder run over chemical storage room door so right side chemical storage room not easily accessible. Maintain 3 ft. clear walking space in pump room.
Gallon jug of muratic acid stored on top of granular tub in pump room. Store chemicals to prevent cross contamination.
Fan not working in chemical storage room. Fan grate degraded due to chemical corrosion on grate. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |