Water quality: disinfectant residual provided by |
No |
No
|
No |
No free chlorine in the spa. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
PH 8.4. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Some eyeball fittings for jets missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door to men’s locker room propped open. .2528(a) Ground level doors shall be self-closing, self-latching. - Intent to suspend item.
Door by shower propped open. .2528(a) Ground level doors shall be self-closing, self-latching. - Intent to suspend item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chemicals added directly to the spa, chemical feeder not functioning properly. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. Chlorine must be added through automatic chemical feeder. - Immediate suspension item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not functioning. .2518(g) Keep flow meter operational. - Intent to suspend item.
Filter pressure gauge damaged. .2519(k) Provide operational pressure gauge on filter. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Bags, shelving, and boxes of chemicals stored by pumps. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |