2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
0.5 ppm free chlorine. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records since Friday 4/4. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for total alkalinity and cyanruic acid if used. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Both skimmers with hair wads and debris. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item. |
|
14
|
4
|
Pool maintenance: spa timer working properly |
No |
No
|
No |
Spa timer > 15 minutes. .2537(b) Spa times shall not exceed 15 minutes without manual resetting. - Intent to suspend item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door to fitness area does not latch. .2528(a) Ground level doors shall be self-closing, self-latching. - Intent to suspend item.
Door to men’s locker room propped open. .2528(a) Ground level doors shall be self-closing, self-latching. - Intent to suspend item.
Door by shower propped open. .2528(a) Ground level doors shall be self-closing, self-latching. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Large puddle of water by pump room door. .2533(d) Pump room floor shall be kept dry and free of standing water.
Boxes of chemicals stored by pumps. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
One faucet in men’s restroom stuck on. .2526(m) Keep restrooms and fixtures clean and in good repair. |