Premises Information

Return to Inspections
NameLA FITNESS
Address3024 PROSPERITY CHURCH RD
 
City/State/ZIP
CHARLOTTE NC 28269
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/5/2026
Final Score @ Grade
24
General CommentsInspection conducted with CPO Nalkus Mincer. *NOTE* Form did not save, signature was lost. Standing water on pool deck. Maintain deck in good condition and sloped to deck drains. Water level an inch or two above the gutter. This makes it difficult to read depth markers on pool walls and gutter does not skim floating debris from pool surface. Maintain proper water level, this is a recurring issue. Flow meter not working. Filter pressure high, no notes in the last month that pool filter was backwashed. Ensure that filters are backwashed as needed and maintenance activities are recorded in the log book. Intent to suspend issued 8) 16) 17) 24)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No PH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.2.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Water level an inch or two above the trough on the gutter. .2518(k) Water level shall be maintained just above the level of the overflow trough on gutter. - Intent to suspend item.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Some doors not self-closing and self-latching. .2528(a) Ground level doors shall be self-closing, self-latching. - Intent to suspend item.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Some benches too close to ladder. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. - Intent to suspend item.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter not functioning. .2518(g) Keep flow meter operational. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Bags, shelving, and boxes of chemicals stored by pumps. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.