5
|
0
|
Ventilation equipment clean, good repair |
No |
No
|
No |
.1311 (b) Ventilation equipment shall be kept clean and in good repair. Observed dust buildup in various ceiling vents throughout facility. Keep ventilation equipment clean. |
|
16
|
3
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water temperatures between 93-100F throughout MC building. Ensure hot water is between 105-116F. Repeat. No hot water violations in AL building. |
|
38
|
0
|
Food service equipment and utensils clean, good repair |
No |
No
|
No |
.1320 (a) All food service equipment and utensils shall be kept clean and in good repair. Observed microwave in AL second floor activity kitchen in need of cleaning. Keep food equipment clean. |