7
|
0
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair. Observed loose toilet seat in room C4 in AL. Maintenance tightened toilet seat during inspection. |
|
8
|
0
|
Toilet rooms free of storage, handwash signs posted |
No |
No
|
No |
.1312 (b) A sign shall be posted in each toilet room for institution employees, directing them to wash their hands after each visit to the toilet room and before returning to work. Observed hall bathroom in AL with no handwashing sign. Maintenance stated that bathroom was recently remodeled. Add sign. |
|
16
|
1.50
|
Hot water between 105°F and 116°F |
No |
No
|
No |
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed water throughout MC building at 98-101F. Observed hall bathroom in AL building at 120F and room C4 bathroom at 80F. Water temperature needs to be between 105-116F. REPEAT |
|
18
|
0.50
|
Drinking fountains clean, good repair |
No |
No
|
No |
.1314 (a) Drinking fountains shall be kept clean and in good repair. Observed drinking fountain in AL hallway that is not functioning. Repair. |