Inspection Date 5/4/2026
Final Score @ Grade
26
General CommentsInspection conducted with CPO Tito Maldonado. Outer rope on ring buoy fraying. Recommend replacing with new US Coast Guard approved ring buoy with attached 47 foot long throw rope at least 1/4 inches in diameter. Permit condition that combined flows of filtration and feature pumps is no more than 224 GPM for limitation of the main drains. Observed 67 and 59 GPM on today’s inspection. Immediate suspension issued 2) 3) Contact Will Harrison (704) 507-6824 for re-inspection once issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item.
3 6 Water quality: pool water pH No No No PH 8.0. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Missing one weir. .2518(k) Replace missing weirs.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No No flow in flow meter for chlorinator. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item.
27 2 Equipment room: filter backwash discharged through an air gap No No No Backwash line extends into backwash pit. .2513(b) Filter backwash shall be discharged through an air gap.
28 2 Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted No No No One of the showers not functioning. .2526(h) Shower(s) shall be provided.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No No toilet paper in men’s restroom. .2526(l) Provide toilet paper and dispensers in restrooms.