| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Test kit with expired reagents and CYA tube not usable due to black staining. Provide new test kit by 6/28. Will verify on return visit. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Black staining on pool floor and wall in some locations. Ensure not mold. Operator stated they have tried to scrub and will not come off. Plaster appears darker than 50% light reflectance. When replastered, ensure new plaster reflects >50% light. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmers with debris/build-up. Keep skimmers clean in order to filtration system to function properly.
One skimmer basket with some damage. Replace skimmer basket furthest from the building. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some chipping paint on pool deck. Some damage to pool deck near step entry and near ladder. Offsets not greater than 1/2". May require repair prior to 2024 operating season. Monitor and repair as needed. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on inlet line to chlorinator. Provide flow meter per NSF specifications. Original construction. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Small leak at filter. Repair leak.
No spare pump basket. Provide spare pump basket for new pump prior to 2024 season. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No lighting in chemical storage room. Fan does not appear to be operable. Providing lighting and ventilation in chemical storage room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash line. Goes through side wall of building. Original construction. Water shall be backwashed through an air gap. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
No shower sign posted on deck. Provide shower sign visible upon entry to the pool. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib for pump room without backflow prevention device. Provide backflow prevention device. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in restrooms. Original construction. Provide hose bib with backflow prevention device. |