Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed 2 weirs missing skimmers. Replace.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed ring bouy in poor condition and throw rope extremely tangled. Replace ring buoy and ensure throw rope is on proper working order at all times. Rope length must be 42’. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Kings III box unable connect to monitoring station or local 911. Repair.
.2530(f) Emergency notification systems (monitoring services) must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer the phone number and address for the phone to 911. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed Blue-White flow meter in pump room. 5% flow meter required. Install 5% flow meter and submit updated PDSC form for approval.
.2518(g) The flow meter installed shall be capable of measuring the minimum turnover rate and permit restriction, if applicable. |