Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NamePAVILION AT UC
Address10425 WHEATSIDE DR
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 5/1/2025
Final Score @ Grade
32
General CommentsPermit denied due to pool pH, chlorine, and emergency phone not working. Contact Mecklenburg County Environmental Health at 980-314-1620 once chlorine and pH at proper levels and when emergency phone is functioning. Drain covers and pump verified as being the same as on PDSC sheet.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No .2535(4) Maintain chlorine at least 1.0 ppm. Chlorine measured 0 ppm in pool. Ensure chemical feeder is functioning so chlorine can be maintained above 1 ppm.
3 6 Water quality: pool water pH No No No .2535(1) Maintain pH at 7.2 to 7.8. pH measured 6.8 during inspection. Maintain pool pH at 7.2 to 7.8.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Tile falling off pool wall in 2 places. Reattach tiles.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Debris present in skimmers. Clean skimmer baskets.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No .2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Ring buoy rope was 55 feet long. CDI - Operator cut rope length to 38 feet.
22 6 Premises: emergency telephone provided No No No .2530(f) Emergency phone shall remain operable. Emergency phone not functioning. Repair phone and ensure it can reach 911.