Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
One main drain by slide missing grate piece. Not in compliance with standard. .2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
.2537(7) Drain covers shall be in good condition and securely attached.
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used.
*Immediate supension |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
One buoy rope tangled at time of inspection.
.2530(a) Lifesaving equipment should be conveniently located and accessible. Operator untangled and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One door not latching or alarmed at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator adjusted to self-closes, self-latch. Corrected. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
One chair within 8ā of deck clearance.
.2522(a) Provide 8 ft of clear walking space around the pool at all times (>1600 sq. ft). Chair moved. Corrected. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone does not audibly ring when called back. Phone shall audibly ring. Phone adjusted during the inspection to audibly ring. Corrected |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored outside of chemical room. One bag of dry chemicals on ground. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water over 110 F in restroom. .2526(i) Water in restrooms shall not exceed 110 F. |