Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
Name500 W TRADE - UPPER SPA
Address500 W TRADE ST
 
City/State/ZIP
CHARLOTTE NC 28202
Premise Type55 - Year-Round Spa
CountyMecklenburg
Inspection Date 9/16/2026
Final Score @ Grade
24
General CommentsHeater not currently operable. New heater installed on roof. Did not view. Requires mechanical permit final prior to use. Mechanical permit pulled but has failed inspection. COM-MEC-26-004330 Intent to Suspend issued for the following: .2528 - window limiters not in place. Install on windows on to pool deck, limited at 4" or less. .2528 - double doors from club room not latching. Repair to self-latch. .2518 - pressure gauges on filters on either end (not center) not operable. One stuck and one reading 0 when pump turned off. Repair filter gauges. .2535 - provide new lid/seal for stick feeder chlorinator.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No July missing records. Records maintained as required for August/September. No temperature logs - no spot in log book for temp logs. Pool heater has not been operable. Provide section in log book for daily temperature logs. CYA reagent low. Replace reagent.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No Some feature bubblers missing fitting. No openings >1/2". Replace fittings where missing.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Window limiters missing from several windows that lead on to pool deck. Secure window limiters to ensure windows do not open greater than 4" on to pool deck. Intent to Suspend issued. Double doors from club room not latching. Repair doors to self-close, self-latch. Intent to Suspend issued.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Back-up stick feeder with lid/seal rusted out. Replace lid for feeder. Used as back-up if automated feeder is not operable. Intent to Suspend issued.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Pressure gauges on two end filters not operable. One stuck and one reading 0 when pump turned off. Replace pressure gauges so operable. Intent to Suspend issued. Property using skimmers to vacuum pool. Pool has (7) skimmers and is not permitted to use the skimmer line to vacuum. Provide portable vacuum. This is a permit restriction for the property that has been set since original construction. Main CPO stated that a portable vacuum is used. Ensure staffing is aware of vacuuming requirements.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chlorine tab bucket in pump room. Store all chemicals in chemical storage room.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No No soap in men's restroom and one soap dispenser without soap in women's restroom. Corrected during the inspection.