2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
No chlorine in pool. Pool has switched to salt. Approved for salt as primary. Provide at least 1.0 ppm through chlorinator. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records not maintained for April. Maintain daily record keeping for chlorine, pH and main drain checks. Weekly record keeping for cyanuric acid and total alkalinity. Intent to Suspend item.
Reagents expired. Provide test kit with new reagents. Intent to Suspend item.
CPO no longer employed at facility. Provide updated CPO information prior to re-opening the pool. CPO card, name, email, phone number. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some tiles missing from pool walls. Repair. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer furthest from steps at deep end not pulling. Provide uniform flow through skimmers so functioning per NSF requirement. Intent to Suspend item.
Baskets with debris/goggles/etc. Ensure skimmer baskets are emptied regularly. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Body hook not secured to pole. Secure body hook to pool. Immediate Suspension issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Main door to pool deck sticking. Door shall self-close, self-latch. Intent to Suspend item. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Address and phone number faded off emergency pool phone signage. Corrected during inspection. Recommend getting permanent signage with address and phone number. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Acid feeder could not be verified to detect flow. Feeder shall detect no flow from pump and turn off with no flow. Intent to Suspend item. |