Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmers with debris at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate had gap greater than 1/2" on right side of latch where sliding tempered glass in fence was moved. Door onto pool deck not latching at time of inspection.
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
Operator moved solid gate glass piece to close gap and inserted putty behind it to keep in place. Door adjusted to self-close-self latch. Corrected. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chairs and furniture within 6' of pool at time of inspection. Furniture within 5' of railings and attachments on pool. Pavers removed from decking at time of inspection, creating offsets greater than 1/2" .2522(a) Provide 6 ft of clear walking space around the pool at all times. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Operator moved pool furniture to create 6' clearance around and workers secured pavers to eliminate offsets. Corrected. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automatic feeder not shutting off chlorine or acid when pump is turned off.
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation.
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation.
Operator unplugged feeder as corrective action. *NOTE: This must remain UNPLUGGED AND DISCONNECTED for permit, must use stick feeder. Contact Marie Daley at 704-507-6806 if automatic feeder is corrected and going to be used. |