3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH < 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Not able to locate pool log book. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, and pool water maintenance. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Records must be kept onsite. - Intent to suspend item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor dirty, mostly with sand and other debris. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer baskets with leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item.
One skimmer basket cracked. .2518(k) Replace missing or damaged skimmer basket. - Intent to suspend item.
Most weirs stuck, missing, or damaged. .2518(k) Install functional weirs. - Intent to suspend item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
All ladders loose, one missing endcaps. .2521 Install ladders per manufacturer instructions. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Post-2010 fencing with some fence sections with gaps > 4" through the fence. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. .2518(g) Keep flow meter operational. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemical storage room fan not functioning. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Pump room fan not functioning. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Floor wet in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Doors to pump room and chemical storage room unlocked. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. |