Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameTRADEMARK COA
Address333 W TRADE ST
 
City/State/ZIP
CHARLOTTE NC 28208
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/14/2022
Final Score @ Grade
24
General Comments9 - No Diving markers not slip-resistant on pool deck in multiple locations. PC with State regional confirmed should be slip-resistant. Replace No Diving with slip-resistant 6"x6" tile prior to 2023 operating permit. 15 - Ring buoy rope fraying near ball. Provide new rope within 30 days. 36 ft. Ring buoy requires replacement prior to 2023 operating season. 22 - 911 operator faint when contacted 911. EHS also faint per 911 operator. Monitor. May require repair if worsens. 28 - Shower signage beginning to fade. May require replacement prior to 2023 operating season. Note: Contrasting color band beginning to fade on steps. May require repair prior to 2023 operating season. If repaired, ensure bands go to edge of steps to side wall. Intent to Suspend issued for: .2535 - maintain daily record keeping for temp and weekly record keeping for TA and CYA .2518 - door shall self-close, self-latch on to pool deck .2530 - trip landscape and move chairs/table so that warning signage is clearly visible from all areas of the pool deck. Jorge Oquendo present during the inspection.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No records for temperature. Maintain daily record keeping for temperature. Cyanuric acid and total alkalinity not recorded weekly. Record weekly. Intent to Suspend issued for temperature record keeping and CYA/TA.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Some debris under the skimmer baskets. Keep clean.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No One door not accessible to verify door self-closes, self-latches. Furthest door to the left. Intent to Suspend issued. Door shall self-close, self-latch.
18 4 Premises: lifeguards present or warning signs posted No No No Warning signage blocked on wall by landscape and signage blocked by tables/chairs near step entry. Warning signage must remain clearly visible from all areas of the pool deck. Intent to Suspend issued.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No No flow meter on chlorinator. If repaired/replaced, install with flow meter.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms >110 F. Maintain at 110 F or below.
33 2 Dressing and sanitary facilities: hose bibbs and floor drains provided No No No No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.