12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
One fitting on pool wall nearest to steps without return fitting. Fitting not threaded. All other returns have fittings. Repair to ensure flow throughout pool.
Vacuum line cover not flush to wall. Corrected during the inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope too long. Corrected to 36 ft. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One door from middle condo not self-closing, self-latching. Repair to self-close, self-latch or self-close with audible alarm. Intent to Suspend issued. Permit will not be issued on May 1 if not corrected prior to.
Windows could not be verified as opening 4" or less due to access. Ensure windows open no greater than 4" on to pool deck from condos. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Adults should not swim alone and Children should not use the swimming pool without adult supervision missing some of the lettering so not a full 1" in height. Corrected with black permanent marker during the inspection. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable. Corrected during the inspection. Design flow of pump is at 100 gpm.
Flow meter only begins at 100 gpm. Ensure correct flow meter installed on the return line. Flow meter not installed per mfg. instructions. Install per mfg. instructions if replaced. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >110 F. Maintain at 110 F or below. |