NameCELSIUS
Address10051 PERIMETER STATION DR
 
City/State/ZIP
CHARLOTTE NC 28216
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 8/1/2024
Final Score @ Grade
16
General CommentsInspection conducted with CPO Bradley Bell. Verified items from previous inspection have been corrected. Conducted pre-permit inspection. Static on emergency phone line. Recommend checking Kings III call box and phone line. Main drains and equalizer line covers expire 5-6-2025. Replace with ANSI/APSP/ICC-16 approved drain covers and provide updated Pool Drain Suction Compliance form to MeckPools@MeckNC.gov for approval prior to expiration. Permit Issued. Paper permit will be issued on our website in 3-5 business days for your records.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Leaves and debris on pool floor. .2537(14) Keep pool surface and pool floor free of debris. - Corrected. Will vacuum the pool this morning before opening it.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One skimmer basket cracked. .2518(k) Replace missing or damaged skimmer basket. - Corrected.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladder extends more than 6" into pool. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. One ladder with loose bottom step. .2521 Install ladders per manufacturer instructions. - This has been noted on previous inspections.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No Eyeball fitting missing by steps. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water. Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.